Products

FireFlex 2300-A01/A02

Movement
High movement capacity
ASTM E-1399
Class I: Thermal
Class II: Wind

Material
High-temperature refractory ceramic fibre
Stainless steel foil sheath

Traffic Frequency per day

Downloads

 

 

Request Price/Sample

Request a Vexcolt sample

Check this product with Vexpert

Description

The Vexcolt FireFlex 2300-A01/A02 is a fire-rated expansion joint tested to EN 1366-4 and classified to EN 13501-2, with 2-hour (120-minute) fire rated integrity for 25–300 mm gaps, 4-hour (240-minute) for gaps up to 100 mm and 3-hour (180-minute) for gaps from 120 to 300 mm. Ceramic fibre infill, stainless steel foil sheath.

Fire Barrier Selection Criteria Load Rating Product Details
Joint
Location
Gap
Width
B (mm)
Movement
Capacity (mm)
Eurocode Rating Product Dimensions Product
Number
± [Total] handtruck forklift car truck Height Sightline Blockout
H1 (mm) H2 (mm)
2 Hour (120 mins) Fire Rated Integrity
Floor – Floor
Floor – Wall
25 ± 12.5 [25] – – – – 175 – – – 2300–A01/2–025–002
35 ± 17.5 [35] 185 – – 2300–A01/2–035–002
50 ± 25 [50] 200 – – 2300–A01/2–050–002
60 ± 30 [60] 210 – – 2300–A01/2–060–002
80 ± 40 [80] 230 – – 2300–A01/2–080–002
100 ± 50 [100] 250 – – 2300–A01/2–100–002
120 ± 60 [120] 270 – – 2300–A01/2–120–002
150 ± 75 [150] 300 – – 2300–A01/2–150–002
200 ± 100 [200] 350 – – 2300–A01/2–200–002
250 ± 125 [250] 400 – – 2300–A01/2–250–002
300 ± 150 [300] 450 – – 2300–A01/2–300–002
4 Hour (240 mins) Fire Rated Integrity
Floor – Floor
Floor – Wall
25 ± 12.5 [25] – – – – 175 – – – 2300–A01/2–025–004
35 ± 17.5 [35] 185 – – 2300–A01/2–035–004
50 ± 25 [50] 200 – – 2300–A01/2–050–004
60 ± 30 [60] 210 – – 2300–A01/2–060–004
80 ± 40 [80] 230 – – 2300–A01/2–080–004
100 ± 50 [100] 250 – – 2300–A01/2–100–004
3 Hour (180 mins) Fire Rated Integrity
Floor – Floor
Floor – Wall
120 ± 60 [120] – – – – 270 – – – 2300–A01/2–120–003
150 ± 75 [150] 300 – – 2300–A01/2–150–003
200 ± 100 [200] 350 – – 2300–A01/2–200–003
250 ± 125 [250] 400 – – 2300–A01/2–250–003
300 ± 150 [300] 450 – – 2300–A01/2–300–003

This product is supplied in various metre lengths depending on the gap width.

Additional information

Gap width(s)

25, 35, 50, 60, 80, 100, 120, 150, 200, 250, 300 mm

Metal type(s)

Stainless Steel foil

Colour(s)

Stainless Steel sheath

Fire barrier

EN 1366-4 tested, EN 13501-2 classified: 2 hours (120 minutes) for 25–300 mm; 4 hours (240 minutes) for 25–100 mm; 3 hours (180 minutes) for 120–300 mm

Waterproofing

EPDM Membrane
Closed-cell Foam

Pre-assembly in factory

Contact Vexcolt

You may also like…